eNet radio energy detector, 1-gang mini
Description
Intended use
- Energy sensor for radio transmission of energy values
- Sensor for load-dependent control of eNet actuators with eNet server
- Operation with eNet server
- Mounting in appliance box according to DIN 49073 in combination with a suitable cover
- Mounting in surface-mounted housing or mounting adapter (ref.-no. FM-EBG) for false ceilings
Product characteristics
- Calculation of the active power and the active energy
- Event or time-controlled transmission of measured value telegrams to the eNet server
- Fully-encrypted radio transmission (AES-CCM) from eNet Server software version 2.0
- Update of the device software
Technical Details
Specification
Rated voltage: AC 230 V ~, 50/60 Hz
Rated load current: 16 A
Peak current (1 s): 80 A
Peak current (1 min): 24 A
Power consumption: max. 0.5 W
Transmission interval: 1 ... 60 min
Ambient temperature: _25 ... +70 ¡C
Connection: screw terminals
- single wire: 0.75 ... 4 mm_
- stranded with ferrule: 0.75 ... 2.5 mm_
Dimensions (¯ x H): 53 x 23 mm
Radio frequency: 868.0 ... 868.6 MHz
Transmitting power: max. 20 mW
Transmission range in free field: typical 100 m
Receiver category: 2
Measuring ranges
- Current: 0 mA ... 16 A
- Accuracy (current): ± 0.5 % of the current value and ± 8 mA
- Voltage: 207 ... 250 V
- Accuracy (voltage): ± 0.5 % of the current value
Transmitted power and energy values
- Active power: _4,000 ... 4,000 W
- Apparent power: 0 ... 4000 VA
- Reactive power: _4,000 ... 4,000 var
- Accuracy (power): ± 0.5 % of the current value and ± 2 W/VA/var
- Active energy: _99,999 ... 99,999 kWh
Properties
Properties
Technology | eNet |
Brand | JUNG |