GIRA
103700
Switching actuator 8-gang/blind actuator 16A - KNX
Product code:
1037 00
Depending on the parameter settings, the actuator can be used as a switching actuator (max. 8-gang) or as a blind actuator (max. 4-gang). Mixed configurations of switching and blind actuator are also possible. For the blind actuator function, two neighbouring relay outputs are combined to form one blind output.
Description
Functions of blind actuator outputs:
- Independent control of up to 4 blind outputs.
- Behaviour after bus voltage failure and return can be set.
- Separately parameterisable movement times with movement time extension for movements into the upper end position.
- Central control of all blind outputs possible.
- Feedback of the curtain position or slat position. Active or passive (object can be read out) cyclical feedback functions.
- Feedback can be delayed until after the return of bus voltage.
- Assignments to up to 5 different safety functions (3 wind alarms, 1 rain alarm, 1 frost alarm), or with cyclical monitoring.
- Forced setting function can be realised for each blind output.
- Solar protection function with fixed and variable curtain or slat positions can be activated.
- Inclusion in scenes possible, maximum of 8 internal scenes can be parameterised per channel.
- Memory function for light scenes.
Functions of Switching Actuator Outputs
- Independent switching of the up to 8 switching outputs.
- NO contact or NC contact operation can be set.
- Behaviour after bus voltage failure and return can be set.
- Central switching function.
- Group feedback for reduction of bus load.
- Active or passive (object can be read out) cyclical feedback function.
- Feedback can be delayed until after the return of bus voltage.
- Logical linking function for each output.
- Block function can be parameterised for each channel. As an alternative, forced setting function for each output.
- Time functions (switch-on, switch-off delay, staircase light function- also with advance warning function).
- Inclusion in scenes possible, maximum of 8 internal scenes can be parameterised per channel.
- Memory function for light scenes.
Technical Details
Specification
- Operating Voltage: 230VAC 50/60Hz
- Power Consumption: Max 3W
- Bus Voltage: KNX Bus 21...30VDC
- Bus Current Consumption: 5mA
- Switching contact: Relay with 8 x zero-voltage closing contacts
- Loading capacity: 230 VAC: 16 A/AC1 16AX
- Max. switch-on current: 800 A, 200 µs, 165 A, 20 ms
- Max Connected load:
- 3000 W ohmic load
- 16 A, max. 140 µF capacitive load
- 1380 VA motors (blind or fan)
- 3000 W light bulbs
- 2500 W HV halogen
- 1200 VA LV halogen, wound transformer
- 1500 W LV halogen, Gira Tronic transformer
- 1000 VA fluorescent lamps, not compensated
- 2300 VA fluorescent lamps duo-circuit
- 1160 VA fluorescent lamps, parallel-compensated
- 1000 W mercury-vapour lamps, uncompensated
- 1160 W mercury-vapour lamps, parallel compensated
- Connection via screw terminals:
- 1.5 to 4mm single-wire
- 2 x 1.5 to 2.5mm single-wire
- 0.75 to 4mm fine-wire without core jacket
- 0.5 to 2.5mm fine-wire with core jacket
Properties
Properties
Technology | KNX |
Brand | GIRA |
Mounting | DIN Rail |
Operating voltage | 230VAC |
Outputs | 8 |
IP rating | IP20 |
Mounting Width | 4MW |
EAN | 4010337042198 |